• High MPPT efficiency up to 99.9% for optimal performance.
• Fast switch time (<20ms) ensures seamless power.
• Wide MPPT voltage range: 125V-850V d.c.
• Supports 125V-800V lithium and lead-acid batteries.
• Harmonic current and voltage are less than 3%, better protection for the power grid and equipment.
Safety, Reliability, Compatibility, Efficiency
SSE-HH40K~60K-P3EU
40K~60KW | Three Phase | High Voltage | IP65
The SSE-HH40K~60K-P3EU Power Conversion System(PCS) integrates local and remote EMS functions to support multiple power grid dispatch modes. The battery voltage ranges from 125V to 800V. It also supports up to 12 parallel machines, and supports SOC balancing function under parallel machines. It supports single-phase 100% unbalanced load operation under off-grid conditions, adapting to various load scenarios.
Enhanced Accessibility & Versatility
Application Scenario
Related Parameters
TECHNICAL SPECIFICATION | |||
Model | SSE-HH40K-P3EU | SSE-HH50K-P3EU | SSE-HH60K-P3EU |
INVERTER INPUT/OUTPUT (GRID) | |||
Rated Power (Input / Output) | 138 kW / 40 kW | 138kW / 50 kW | 138 kW / 60 kW |
Rated Voltage | 380 / 400 V a.c., 3W+N+PE | ||
Rated Frequency | 50 Hz / 60 Hz | ||
Power Factor Range | 0.8 leading~ 0.8 lagging | ||
Switch Time | <10 ms | ||
Max. Continuous Current (Input / Output) | 200 A a.c. / 58 A a. c. | 200 A a. c. / 72 A a. c. | 200 A a. c / 87 A a. c. |
Max. Output Overcurrent Protection | 123 A a. c. | 153 A a. c. | 185 A a. c. |
BATTERY | |||
Battery Type | Lithium / Lead-acid | ||
Battery Voltage Range | 125 ~ 800 V d.c. | ||
Rated Battery Voltage | 200 V d. c. | 250 V d. c. | 300 V d. c. |
Max. Charge Current | 2*100 A d. c. | ||
Max. Discharge Current | 2*100 A d. c | ||
Reverse Connect Protection | Yes | ||
PV INPUT | |||
No. of MPPT Tracker/Strings | 4 / 2+2+2+2 | ||
Max. PV Array Power | 68 kW | 85 kW | 100 kW |
Max. DC Voltage | 1000 V d. c. | ||
MPPT Voltage Range | 150 ~ 850 V d. c. | ||
Start-up Voltage | 150 V d. c. | ||
Max. Input Current | 40 A d. c. | ||
Isc PV (Absolute Maximum) | 60 A d. c. | ||
AC OUTPUT (EPS) | |||
EPS Rated Output Voltage | 380 / 400 V a.c., 3W+N+PE | ||
EPS Rated Output Frequency | 50 Hz / 60 Hz | ||
EPS Rated Output Active Power | 40 kW | 50 kW | 60 kW |
EPS Rated Output Apparent Power | 44 kVA | 55 kVA | 66 kVA |
EPS Rated Output Current | 58 A a. c. | 72 A a. c. | 87 A a. c. |
Overload Capacity (Off Grid) | 110% 30s / 120% 10s / 150% 0.2s | ||
EFFICIENCY | |||
MPPT Efficiency | 99.9% | ||
Euro-efficiency | 97.5% | ||
Max. Efficiency | 98.5% | ||
PROTECTION & FEATURE | |||
Insulation Monitoring | Yes | ||
Residual Current Monitoring | Yes | ||
Parallel Function | Yes, up to 6pcs | ||
Protection Degree | IP65 | ||
Certifications | CE10-21, EN 50549-1, VDE-AR-N 4105, UNE 217002, NTSTYPEA, G99, AS/NZS 4777.2 | ||
Other Protection | Ground Fault Current Monitoring, Earth Fault Detection, Residual Current (RCD) Detection | ||
GENERAL PARAMETER | |||
Storage Temperature | -40℃ ~ +70℃ | ||
Operating Temperature | -25℃ ~ +60℃ (>+45℃, Derating) | ||
Humidity | 0% ~ 95% (Non-condensing) | ||
Operating Altitude | 4,000 m (>2,000 m Derating) | ||
Noise | <45 dB | ||
Dimensions (W*H*D) | 530*850*290 mm | ||
Shipping Dimensions (L*W*H) | 680*1050*400 mm | ||
Machine Weight / N.W. | 75 kg | ||
DISPLAY & COMMUNICATION | |||
Display | LED+APP | ||
Interface | RS485 / WiFi / CAN / DRM (Optional: Bluetooth / LAN / 4G / Meter) |